Another stuck check valve. This time on a unit that never operated in cooling before until now.
When I was attempting to read my hot gas temp before and across "Check Valve A", I was momentarily puzzled on how my compressor discharge gas temperature was dropping from 140 degrees down to just above ambient at the coil manifold assembly entering the outdoor coil! WTF???
Turns out it was a stuck check valve and a with the very low flow through the compressor, some liquid was being carried through and was flashing off quickly to drop the hot gas down to near ambient just a few feet away form the compressor! How often do you see that?
While doing my revering under pressure trick with some tapping on the check valves, it returned to normal. However, I did not notice the instant it did due to the fieldpiece suction probe locking up and only displaying the low pressure I encountered when it was restricting.
I had to restart my fieldpiece probes and app to clear that up.